Details of the IEC 61850 client

"Quality" and "Time" related Information

The attributes "Quality" (q) and "Time" (t) are available for following Common Data Classes (CDCs). Please note that the information "Quality" and "Time" is not available for all attributes, e.g. the attribute "instMag" of the class "MV" only provides the information "Quality" and not "Time".

CDC Data attribute q applies to Data attribute t applies to
SPS stVal
DPS stVal
INS stVal
ENS stVal
ACT general, phsA, phsB, phsC, neut
ACD general, dirGeneral, phsA, dirPhsA, phsB, dirPhsB, phsC,dirPhsC, neut, dirNeut
BCR actVal, frVal actVal
HST hstVal
VSS stVal
MV instMag, mag, range mag, range
CMV instCVal, cVal, range cVal, range
SAV instMag
HMV Har
HWYE phsAHar, phsBHar, phsCHar, neutHar, netHar, resHar
HDEL phsABHar, phsBCHar, phsCAHar
SPC stVal
DPC stVal
INC stVal
ENC stVal
BSC valWTr
ISC valWTr
APC mxVal
BAC mxVal
SEC - cnt

Quality type definition for bits (0-12)

Table 1. Quality type definition
Attribute name Attribute type Value/Value range M/O/C
PACKED LIST
validity CODED ENUM good | invalid | reserved | questionable M
detailQual PACKED LIST M
overflow BOOLEAN DEFAULT FALSE M
outOfRange BOOLEAN DEFAULT FALSE M
badReference BOOLEAN DEFAULT FALSE M
oscillatory BOOLEAN DEFAULT FALSE M
failure BOOLEAN DEFAULT FALSE M
oldData BOOLEAN DEFAULT FALSE M
inconsistent BOOLEAN DEFAULT FALSE M
inaccurate BOOLEAN DEFAULT FALSE M
source CODED ENUM

process | substituted

DEFAULT process

M
test BOOLEAN DEFAULT FALSE M
operatorBlocked BOOLEAN DEFAULT FALSE M

WinCC OA IEC 61850 error codes

Error codes Description
100 Success
101 NULL Server
102 Not Connected
103 No Connection
104 Flow controlled
105 Max Services Exceeded
106 No Read data
107 Memory
108 Encoding
109 Bad Transaction
110 No Transaction
111 Connection Closed
112 Timed Out
113 Connection State
114 Application Error
115 Bad Parameters
116 Confirmed Error
117 Reject
118 No Authentication
119 Conclude with services outstanding
200 object-invalidated
201 hardware-fault
202 temporarily-unavailable
203 object-access-denied
204 object-undefined
205 invalid-address
206 type-unsupported
207 type-inconsistent
208 object-attribute-inconsistent
209 object-access-unsupported
210 object-non-existent
211 object-value-invalid
212 Unknown

RCB States

State Description
0

Not active

Target device online, RCB not enabled/reserved

1

Reserved

Target device online, RCB reserved

2

Active

Target device online, RCB enabled and active

3

Enable failed

Manual enable failed, RCB in use

4

Enable failed

Automatic enable exhausted maximum number of retries (refer to reportEnaMaxRetry), RCB in use

5

Not connected

Target device not connected

6

Initializing

State on first enable or first reserve

7

Reserving

Try reserving, in case of BRCB not supporting resvTms the availability is checked

8

Enabling

Try enabling the RCB

9

Enable retry

Indicate retry for enabling the RCB

10

Manual enable failed

Manual enable failed (error on writing attribute)

11

Auto enable failed

Automatic enable failed (error on writing attribute)

12

Initialized

RCB has been inizialized from file

13

Initialization failed

Initializing RCB failed

14

Checking attributes

Checking RCB attributes prior to enabling

15

Data set mismatch

Indicates a mismatch in data set configuration in case the data set attribute is not writeable.

16

Attribute mismatch

Indicates a mismatch in the RCB attribute setting of any non-writable RCB attribute.

17

Init ready

RCB attribute settings received from the device

18

Init error

Reading RCB attributes from device failed

19

RPT_PURGE_ERROR

Sending purge buffer failed

20

RPT_PURGING_ON_CONF_CHANGE

Purging buffer in case a BRCB is enabled with a new dataset

21

RPT_REQUEST_CONFIG

Sending RCB attribute write requests to device

22

RPT_WRITING_CONFIG

Prior to enabling, transitions to enabling if all write requests were successful

23

RPT_REQUEST_ENABLE

Set when all checks have been passed, RCB is ready to be enabled

24

RPT_DYN_DATSET_RETRY

Waiting for dynamic dataset to be written (UI displays RPT_ENABLE_RETRY)

25

RPT_DISABLING

Waiting for confirmation from device that RCB has beeb disabled

26

RPT_RELEASING

Waiting for confirmation from device that RCB has been released

RCB Response Codes

Response Code Description
0 Success
1 object invalid
2 hardware fault
3 temporarily unavailable
4 object access denied
5 object undefined
6 invalid address
7 type not supported
8 type inconsistent
9 object attribute inconstant
10 object access unsupported
11 object not existent
12 object value invalid
13 NULL server
14 not connected
15 No connection
16 flow controlled
17 max. services exceeded
18 no read data
19 memory
20 encoding
21 bad transaction
22 no transaction
23 connection closed
24 time out
25 connection state
26 application error
27 bad parameters
28 confirmed error
29 reject
30 no authentication
31 conclude with services outstanding

File Transfer Response Code

Response Code Description
0 Read directly successful
1 NULL server
2 Not connected
3 No connection available
4 Flow controlled
5 Max services exceeded
6 No read data
7 Memory
8 Encoding
9 Bad transaction
10 No transactions
11 Connection closed
12 Timed out
13 Connection state
14 Application error
15 Bad parameters
16 Confirmed error
17 Reject
18 No authentication
19 Conclude with services outstanding
51 File download success
52 Data count does not match while reading directory
53 File directory empty
54 File could not be opened
55 File path not found
56 Command failed as device is not active
57 Command failed due to server returned null pointer

Debug Flags

-report ALL

Provides information on configuration and status for

  • all created devices
  • every enabled RCB

Inactive RCBs are displayed as „disabled…"

„Enabled" refers to the Engineering Tool's configuration settings and not to the activation state of the RCB on the device.

WCCOAiec618501:<<<<<<<<<< IEC 61850 (num  <driver number>) Information >>>>>>>>>>
WCCOAiec618501:---------------------------------------------------
WCCOAiec618501:Report for device <OA device name> (IP:<IP>:<port>)
WCCOAiec618501:Connection state  : <state>
WCCOAiec618501:Browse state      : <state>
WCCOAiec618501:   Configuration
WCCOAiec618501:   * Device active             :  <0/1>
WCCOAiec618501:   * Connect passive           :  <0/1>
WCCOAiec618501:   * Read complete buffer      :  <0/1>
WCCOAiec618501:   * Authentication            :  <0/1>
WCCOAiec618501:   * Enable RCB configuration  : <0/1>
WCCOAiec618501:Number of Report Control Blocks: <number of configured RCBs>
WCCOAiec618501:-- RCB <RCB name>
WCCOAiec618501:   State          :  <Driver internal state>
WCCOAiec618501:   State at device: <Actual state at device>
WCCOAiec618501:   Response code  : <Response code>
WCCOAiec618501:   Configuration
WCCOAiec618501:   * ReportID      : <Report ID>
WCCOAiec618501:   * Buffered      : <0/1>
WCCOAiec618501:   * Indexed       : <0/1>
WCCOAiec618501:   * Max enable    : <Maximum number of instances>
WCCOAiec618501:   * Reserve       : <0/1>
WCCOAiec618501:   * Enable        : <0/1>
WCCOAiec618501:   Trigger options
WCCOAiec618501:   + <Trigger option>: <0/1>
WCCOAiec618501:   + Integrity period: <Integrity period>
WCCOAiec618501:   + Buffer time     : <Buffer time>
WCCOAiec618501:   Optional fields
WCCOAiec618501:   ~ <Optional field>    : <0/1>
WCCOAiec618501:   Dataset name : <Dataset name>
WCCOAiec618501:   Is dynamic   : <Yes|No>
WCCOAiec618501:   Is persistent: <Yes|No> (only shown for dynamic datasets)
WCCOAiec618501:   --------------
WCCOAiec618501:-- RCB <RCB name>
WCCOAiec618501:   Disabled...
WCCOAiec618501:   --------------
WCCOAiec618501:------------------ End IEC device -----------------
WCCOAiec618501:<<<<<<<<<<<<<<<<<< End IEC 61850 >>>>>>>>>>>>>>>>>>

-report ALL -dbg DATASET

If -report ALL is used with option -dbg DATASET, only detailed information on datasets is provided. In addition to the information provided by -report ALL, a list of dataset elements is given for every enabled RCB.

WCCOAiec618501:<<<<<<<<<< IEC 61850 (num <driver number>) Information >>>>>>>>>>
WCCOAiec618501:-- Dataset information; printed only for enabled RCBs
WCCOAiec618501:---------------------------------------------------
WCCOAiec618501:Dataset report for device <OA device name> " (IP:<IP>:<port>)IP:192.168.154.76:102) "
WCCOAiec618501:-- RCB <RCB name>
WCCOAiec618501:   Dataset name : <dataset name>
WCCOAiec618501:   Is dynamic   : <Yes|No>
WCCOAiec618501:   Is persistent: <Yes|No> (only shown for dynamic datasets)
WCCOAiec618501:   Members: <List of dataset members>
WCCOAiec618501:   --------------
WCCOAiec618501:------------------ End IEC device -----------------
WCCOAiec618501:<<<<<<<<<<<<<<<<<< End IEC 61850 >>>>>>>>>>>>>>>>>>

-dbg DEBUG_DRV_CONF

Provides information on

  • creating devices and RCBs
  • initializing routines of devices and RCBs
  • requests for configuration and control of RCBs on the device

The following debug output also shows the startup routine of the driver:

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.665, DEBUG_DRV_CONF, "New server <OA device name> added"

=> Device <OA device name> created

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.668, DEBUG_DRV_CONF, "Server connection <OA device name>  initializing..."

=> Initializing of device <OA device name> is started

WCCOAiec618502:WCCOAiec61850(2), 20152017.05.27 15:32:03.671, DEBUG_DRV_CONF, "New RCB: <RCB name> added for server <OA device name>"

=> RCB < RCB name > created

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.681, DEBUG_DRV_CONF, "Server connection <OA device name>  initialized"

=> Initializing device <OA device name> is completed

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.685, DEBUG_DRV_CONF, " Check remote device <OA device name> , send request to <RCB name>"

=> Query properties of device <OA device name> because of <RCB name> attribute

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.695, DEBUG_DRV_CONF, " Updating ResvTms data type for server <OA device name>"

=> Update properties of device <OA device name>

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.697, DEBUG_DRV_CONF, "<OA device name> anvil_8102, Data type for resvTms could not be read from device, using default."

=> <OA device name> does not support resvTms or a buffered RCB is configured

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.700, DEBUG_DRV_CONF, "<OA device name> Request: Get attribute settings for RCB: <RCB name>"

=> Query configuration of RCB <RCB name>

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.720, DEBUG_DRV_CONF, " ----- Extract attribute settings of RCB: <RCB name> from server <OA device name> -----"

=> Start evaluating the configuration of <RCB name> from server <OA device name>.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.722, DEBUG_DRV_CONF, " Received attribute settings <RCB Konfiguration>"

=> Output of configuration settings

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:03.740, DEBUG_DRV_CONF, " <OA device name>, Request:  Write <attribute name> [attribute value] for RCB <RCB name>"

=> Write the value [attribute value] of attribute <attribute name> for <RCB name> of device <OA device name>. [attribute value] is not available for all attributes of an RCB.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:32:05.700, DEBUG_DRV_CONF, " <OA device name>: remove RCB <RCB name>"

=> Removed RCB <RCB name> (via RCB Management Panel)

-dbg DEBUG_DRV_SENT

Shows messages sent to the server.

// Startup

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:38:56.426, DEBUG_DRV_SENT, "Identify request send to server <OA device name>"

=> Sent on startup and as alive telegram

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:39:02.531, DEBUG_DRV_SENT, "Write <Boolean|String|Octet String|Integer|UInteger> value for <OA device name>/<LN>$<FC>$<RCB name>$<BufTm|DatSet|IntglPd|RptID|EntryID>"

=> Write an attribute of <RCB name> when enabling the RCB

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:39:02.541, DEBUG_DRV_SENT, "Write Trigger Options for <OA device name>/<LN>$<FC>$< RCB name >$TrgOps"

=> Write trigger settings of <RCB name> when enabling the RCB

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:39:02.545, DEBUG_DRV_SENT, "Write Optional Fields for <OA device name>/<LN>$<FC>$< RCB name >$ OptFlds"

=> Write optional field settings of <RCB name> when enabling the RCB

// Device Browsing

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:40:56.433, DEBUG_DRV_SENT, "Logical device list request sent to server <OA device name>"

=> Request a list of all LDs of <OA device name> =[Request 1]

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:40:66.429, DEBUG_DRV_SENT, "Send MMS tag list request for Logical device <LD> to server <OA device name>"

=> Request a list of all DOs (tag list) from logical device <LD> of <OA device name> =[Request 2]

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:40:76.452, DEBUG_DRV_SENT, "Send dataset list request for Logical Device <LD> to server <OA device name>"

=> Request list of all datasets configured for <LD> of <OA device name> =[Request 3]

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:40:56.595, DEBUG_DRV_SENT, "Send Dataset attribute request for <data set> to server <OA device name>"

=> Request dataset attributes of dataset <data set> of <OA device name> =[Request 4]

// General write requests

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:41:13.035, DEBUG_DRV_SENT, "Write mms tag value for <OA device name>/<LN>$FC$<DO>$<DA>

=> Sent value to the data attribute

// Commands

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:41:13.035, DEBUG_DRV_SENT, "Write Control Struct <OA device name>/<LN>$CO$<DO>$Oper"

=> Send switching command (Control Structure) for controllable object <DO> of <OA device name>/<LN>

-dbg DEBUG_DRV_RCVD

Provides either the type of received message or the source address on the device for received telegrams.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.996, DEBUG_DRV_RCVD, " Identify response from server <OA device name>"

=> Response to alive telegram of <OA device name>.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.998, DEBUG_DRV_RCVD, "Value received from <OA device name>.<LD>/<LN>$<FC>$<DO>$<DA>, write to OA"

=> Response to poll request, received value for <OA device name>.<LD>/<LN>$<FC>$<DO>$<DA> and sent to the driver framework

// Device Browsing

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.354, DEBUG_DRV_RCVD, "Received Logical device list (class 9) from server <OA device name>"

=> Received list of LDs from <OA device name>, response to Request 1

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.355, DEBUG_DRV_RCVD, "LD name <LD>"

=> Logical Device <LD>, response to Request 1

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.688, DEBUG_DRV_RCVD, " Received MMS tag list for Logical  device <LD> (class 0) from server <OA device name>"

=> Received tag list of logical device <LD> from server <OA device name>, response to Request 2.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.690, DEBUG_DRV_RCVD, " Tag name <<LN>>"

=> Logical node <LN>, response to Request 2

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.691, DEBUG_DRV_RCVD, " Tag name <<LN>$<FC>>"

=> Functional Constraint <FC> of logical node <LN>, response to Request 2

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.691, DEBUG_DRV_RCVD, " Tag name <<LN>$<FC>$<DO>>"

=> Data object <DO> of logical node <LN>, response to Request 2

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.692, DEBUG_DRV_RCVD, " Tag name <<LN>$<FC>$<DO>$<DA>>"

=> Data attribute <DO>$<DA> of logical node <LN>, response to Request 2

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.705, DEBUG_DRV_RCVD, "Received dataset list for Logical device IED1LogicalDevice1 (class 2) from server <OA device name>"

=> Received list of datasets of logical device <LD> from server <OA device name>, response to Request 3

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.711, DEBUG_DRV_RCVD, "Dataset name <DatSet>"

=> Dataset <DatSet>, response to Request 3

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:25:51.715, DEBUG_DRV_RCVD, "Read attribute response for dataset <DatSet> from server <OA device name> is success"

=> Reading dataset attributes of dataset <DatSet> from server <OA device name> was successful, response to Request 4

-dbg DEBUG_DRV_COMMAND

Provides information on service requests which are using the Control Model.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:45:16.733, DEBUG_DRV_COMMAND, "Writing Controllable Object <LD>/<LN>$<FC>$<DO>$<DA> to the Server: <OA device name> with following values:
WCCOAiec618502:Control value: <value to be written>
WCCOAiec618502:Ctlnum value: <control number> WCCOAiec618502:Test: <0/1>
WCCOAiec618502:Check: <no-check|synchrocheck|interlocking|both>
WCCOAiec618502:Originator: <host name>_<project name>_<driver number>
WCCOAiec618502:Category: <originator category>"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:45:16.756, DEBUG_DRV_COMMAND, "Write Response for Controllable Object <LD>/<LN>$<FC>$<DO>$<DA> from Server: <OA device name> is Success"

-dbg DEBUG_DRV_REPORT

Shows which values of an RCB are sent to WinCC OA. There is only output for configured addresses.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:50:47.528, DEBUG_DRV_REPORT, "Write data received through report to: <OA device name>.<LD>/<LN>$<FC>$<DO>$<DA>"

-dbg DRV_REPORT_CONFIG

Allows to track requirements for an RCB on the device (e.g. changes to configuration and activation).

// Activation and configuration

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:59:43.403, DRV_REPORT_CONFIG, "<OA device name>, Start all RCBs at remote state: <remote state>"

=> Starting enabling routines for all RCBs of <OA device name>. On startup, the device state is <remote state>. Possible states:

  • REMOTE_UNKNOWN, // startup or retry if not checked
  • REMOTE_UNREACHABLE, // tried but failed
  • REMOTE_PENDING, // request sent
  • REMOTE_CHECKED, // done
  • REMOTE_CHECK_INCOMPLETE // Either rsvTmsDataType or iec edition could not be detected
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:59:43.608, DRV_REPORT_CONFIG, "<OA device name> , State change for <RCB name> reserve is <0|1>| enable is <0|1>"

=> The driver received the request (DP interface or internal logic) to change the state of RCB <RCB name>. Which reserve or activation state is necessary depends on the values of „reserve is" and „enable is"

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:59:45.379, DRV_REPORT_CONFIG, "<OA device name> , Request: configure dataset <dataset name> for RCB <report ID>"

=> On enabling RCB <report ID> it is requested to configure the RCB with dataset <dataset name>

//Request: " Process RCB response" confirms that a request to the RCB is processed by the device. There is no indication whether the request was successful.

The "index" field shows the instance number for instanced RCBs. Otherwise the field is empty. The "is manual" field shows whether the request was triggered by data point interface (1) or driver logic (0).

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:59:43.363, DRV_REPORT_CONFIG, "Process RCB response: device: <OA device name>| report: <report ID>|index: | request: Reserve RCB| attribute: Resv| value: <0/1>1| is manual: 1"

=> Request to reserve (1) the RCB <report ID> or cancel the reservation (0)

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:59:43.376, DRV_REPORT_CONFIG, "Process RCB response: device: <OA device name>| report: <report ID>| index: | request: Read RCB Attributes| attribute: <RCB name>| value: 1| is manual: 1"

=> Request to read the attributes of RCB <report ID>

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:59:43.411, DRV_REPORT_CONFIG, "Process RCB response: device: <OA device name>| report: <report ID>| index: | request: Write RCB Attribute| attribute: <BufTm|DatSet|IntglPd|OptFlds|RptID|TrgOps>|  value:1 is manual: 1"

=> Request to write an attribute of RCB <report ID>

// Acknowledgements

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:59:43.412, DRV_REPORT_CONFIG, "OK: <BufTm|DatSet|IntglPd|OptFlds|RptID|TrgOps>"

=> Writing the attribute was successful

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 15:59:43.379, DRV_REPORT_CONFIG, "Attribute read OK: <RCB name>"

=> Reading an attribute of <RCB name> was successful

-dbg DRV_REPORT_RCV

Provides information on received reports. All elements are displayed, whether or not an address is configured.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:04:25.656, DRV_REPORT_RCV, "---------------- New report <report ID> received"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:04:25.659, DRV_REPORT_RCV, "Type: Unbuffered"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:04:25.659, DRV_REPORT_RCV, "Sequence Num: <number>"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:04:25.660, DRV_REPORT_RCV, "Reason: <DATA_CHANGE|DATA_FREEZE|GEN_INTER|INTEGRITY|QUALITY_CHANGE>"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:04:25.669, DRV_REPORT_RCV, "Element at index <0..n>: <logical device name>/<LN>$<FC>$<DO> WCCOAiec618502:"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:04:25.671, DRV_REPORT_RCV, "     Attribute at index <0..n>: <LN>$<FC>$<DO>$<DA>"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:04:25.697, DRV_REPORT_RCV, "---------------- Report <report ID> done

-dbg DRV_REPORT_PROCESS

Provides information on the processing of reports. All elements are displayed, whether or not an address is configured.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:06:32.003, DRV_REPORT_PROCESS, "---------------- Start processsing report <report ID>"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:06:32.004, DRV_REPORT_PROCESS, "Element <LD>/<LN>$<FC>$<DO>"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:06:32.005, DRV_REPORT_PROCESS, "       Attribute <LN>$<FC>$<DA>$<DO>"
WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:06:32.022, DRV_REPORT_PROCESS, "----------------  report <report ID> done

-dbg DRV_DATASET_CONFIG

Provides information on static and dynamic datasets.

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:09:38.077, DRV_DATASET_CONFIG, "<OA device name>: add new dataset <dataset name>"

=> Added dataset <dataset name>" to the driver

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:09:38.406, DRV_DATASET_CONFIG, "<OA device name>: add dataset attributes for <dataset name>"

=> Added attributes to dataset elements of dataset <dataset name>" (this is only valid for datasets of type FC, i.e. datasets whose elements are data objects)

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:09:45.795, DRV_DATASET_CONFIG, "<OA device name>, Request: Write dynamic dataset <dataset name> triggered  by RCB <RCB name>"

=> Request to write the dataset <dataset name> (which is assigned to RCB <RCB name>) on the device

WCCOAiec618502:WCCOAiec61850(2), 2017.05.27 16:09:45.801, DRV_DATASET_CONFIG, "<OA device name> , Dataset <name> busy, RCB <report ID>"

=> Dataset <dataset name> which is assigned to RCB <RCB name> cannot be written. This message is displayed if several RCBs are using the same dynamic dataset. The dataset is written on enabling the first RCB. During this process, the message is shown when activating the other RCBs. The RCBs are enabled as soon as the dataset is written on the device.