Settings for the WinCC OA mobile UI application and the Desktop UI.
[webClient] clientProjExt
- Type
- uint
- Default
- 0
- Range
- 0-2
Defines the name of the cache directory for the Desktop/Mobile UI: 0 - projectName
(default) 1 - projectName_ServerName 2 -
projectName_reduServerName1_reduServerName2
[webClient] clientSideAuth
- Type
- bool
- Default
- 1
- Range
- 0|1
The entry "clientSideAuth" = 1 enables authentication on the client-side. The entry
"clientSideAuth" = 0 enables the server-side authentication. See Serverside
Authentication, Basics
[webClient] httpAuth
- Type
- Bool
- Default
- 0
- Range
- 0|1
Specifies whether authentication is used for the http server or not. Note: If
setUserId() is called and httpAuth is activated (1) the ULC UX logs out.
[webClient] httpPort
- Type
- uint
- Default
- 80(Windows), 8080(Linux)
- Range
- 0-65535
Defines the http port that is used for the unsecured http communication between server
and client. Per default the http port 80 is used. No config entry must be set to use the
default port. Using port 0 will deactivate the http communication.
[webClient] httpsPort
- Type
- uint
- Default
- 443(Windows), 8079(Linux)
- Range
- 0-65535
Defines the https port that is used for the secured https communication between server
and client. Using port 0 will deactivate the https communication.
[webClient] lowestAutoManNumMobileUI
- Type
- unsigned
- Default
- 200
- Range
- 1-255
The entry "lowestAutoManNumMobileUI" defines the lowest manager number for the mobile UI
clients.
[webClient] mobileRootPanel
- Type
- string
- Range
- <relative path>/<panelname>.pnl
Defines the start-up panel for the mobile application. If the config entry is not set,
the login.pnl is displayed.
[webClient] rootPanel
- Type
- string
- Range
- <relative path>/<panelname>.pnl
Defines the start-up panel for the UI. If the config entry is not set, the login.pnl is
displayed.