[SiemensCerberus]
Settings for the Cerberus driver
[SiemensCerberus] ComPort
- Type
- string,string
Format:
ComPort= "<COM port>" "<baud rate>"
The COM port and baud rate must be set to your specific hardware and MK7022 settings. A
null modem cable, with 2 and 3 crossed, is used to connect the RS232 COM port and the
MK7022.
Example:
ComPort= "COM2" "9600,E,7,2"
[SiemensCerberus] DMSAddress
- Type
- int,string
Format:
DMSAddress= <DMA Address (number)> "<"BMA" or "EMA" or "PROTO" or "GAS">"
Example:
DMSAddress = 118 "BMA"
DMSAddress = 119 "EMA"
DMSAddress = 117 "PROTO"
In the example you see the address 118 which is a Cerberus Fire system denoted by the
"BMA" string. The DMS Address 117 is the "PROTO". This address is obligatory and is the
protocol handler for the MK7022. The order of the DMAAddress config entries is not
important, i.e. the 117 could be the first entry in the list.[SiemensCerberus] pollTime
- Type
- int