[SiemensCerberus]

Settings for the Cerberus driver

[SiemensCerberus] ComPort

Type
string,string
Sets the COM port and the baud rate.

Format:
ComPort= "<COM port>" "<baud rate>"
The COM port and baud rate must be set to your specific hardware and MK7022 settings. A null modem cable, with 2 and 3 crossed, is used to connect the RS232 COM port and the MK7022.

Example:
ComPort= "COM2" "9600,E,7,2"

[SiemensCerberus] DMSAddress

Type
int,string
Defines the DMS address.

Format:
DMSAddress= <DMA Address (number)> "<"BMA" or "EMA" or "PROTO" or "GAS">"

Example:
DMSAddress = 118 "BMA"
DMSAddress = 119 "EMA"
DMSAddress = 117 "PROTO"
In the example you see the address 118 which is a Cerberus Fire system denoted by the "BMA" string. The DMS Address 117 is the "PROTO". This address is obligatory and is the protocol handler for the MK7022. The order of the DMAAddress config entries is not important, i.e. the 117 could be the first entry in the list.

[SiemensCerberus] pollTime

Type
int
Is an internal setting for the protocol state machine. It should not get under 100.