Pump2 data point type

This data point type can be used to display a controllable pump. There are two different versions to choose from:

  • Type 1: one speed (only the address of .state.on is enabled)

  • Type 2: two speeds (addresses .state.on and .state.on_2 are enabled)

Faults and operating mode messages can be displayed as an option. Please refer to the type table for the command code.

Element Data type Description
alert.ControlFuse bool Control fuse fault
alert.converter bool Frequency converter fault
alert.flow bool Flow indicator fault
alert.motorSwitch bool Motor protective switch fault
alert.motorTherm bool Fault in motor thermistor protection
alert.overload bool Overload fault
alert.pressure bool Pressure monitor fault
alert.runDry bool Running dry fault
alert.speed bool Speed monitoring fault
alert.sumalertPLC bool External group alert
alert.sumalert string Internal group alert
cmd.on int on=1 Off, on=2 On, on= 4 second speed
cmd.mode typref Reference of the MODE_CMD data type, auto = 2 manual mode, auto = 1 automatic mode
para.speed float Required speed
state.on bool On
state.on_2 bool On 2nd speed
state.off bool Off
state.mode typref Reference of the MODE_STATE data point type
value.powerCon float Power consumption
value.speed float Speed

Associated symbols

Symbol Symbol name Description
Compressor This symbol represents a compressor
Fan This symbol represents a fan
Macerator This symbol represents a macerator
Pump This symbol represents a pump