Settings for the Modbus driver
[mod] addUnicosMarker
- Type
- int
- Default
- -1
- Range
- -1..65535
Defines the reference number that is used by the driver to decide whether it is a Modbus
or a UNICOS frame. The entry is deactivated by default.
[mod] aliveInterval
- Type
- unsigned
- Default
- 10 [s]
- Range
- >= 0
Specifies an alive interval for the driver in seconds. The Value 0 means that no
keep-alive messages are sent. A value > 0 means that the driver sends a read request
to all connected PLCs every aliveInterval seconds.
[mod] aliveTimeoutMsg
- Type
- unsigned unsigned
- Default
- 3 1
Specifies the function code and the reference number for the alive request.
[mod] autoGQ
- Type
- bool
- Default
- 1
- Range
- 0|1
Defines whether general queries shall be executed automatically. 0 = no automatic general
query 1 = automatic general query when connection is established
[mod] idleCloseTimeout
- Type
- unsigned
- Default
- 0 [s]
- Range
- >= 0
The driver closes the connection to the PLC if the connection is idle for the specified
time (in seconds). This is done only for connections in master mode.
[mod] littleEndianRegister
- Type
- int
- Default
- -1
- Range
- -1|0|1
Defines the order of registers (16bit words) within 32bit or 64bit process data.
Possible values:
- -1 - No preferred value is defined. (Default).
- 0 - bigEndianRegister is preferred.
- 1 - littleEndianRegister is preferred.
[mod] maxConnRetryNumber
- Type
- unsigned
- Default
- 0
- Range
- >= 0
Specifies how many times the driver retries to establish a connection when sending a
telegram, if the connection request fails.
[mod] maxGap
- Type
- uint
- Default
- 16
- Range
- 0..100
If the difference of two consecutive address reference numbers is lower or equal the
value in maxGap, than these addresses are grouped together in one poll block. If not, then a
second poll block is created. This entry provides the poll query optimization.
[mod] maxPendingRequests
- Type
- unsigned
- Default
- 1
- Range
- 1..8
The maximum number of outstanding requests without response. The entry can be used for
sending more requests in advance in order to speed up the communication. If you set the
value of the entry to higher than 1, you have to verify that the PLCs controlled by the
driver are able to handle several requests.
[mod] maxQueueSize
- Type
- int
- Default
- 256
Defines the size of the request queue for master mode. For example maxQueueSize = 1000
[mod] maxRequestRetryNumber
- Type
- unsigned
- Default
- 0
- Range
- >= 0
Specifies the number of retries for a requests if a response is missing.
[mod] onlyActivePolls
- Type
- bool
- Default
- 0
- Range
- 0|1
Only the active driver polls in a redundant system
[mod] plc
- Type
- string
Obsolete since WinCC OA version 3.9. The datapoint name of PLC the driver cares for. An
entry must exist for each PLC (e.g. plc = "_Mod_Plc_2"). The datapoints are created
automatically by defining the parameters in the parameterization panel of the Modbus/TCP
driver (see chapter Parameterization panel of the Modbus/TCP driver).
[mod] pollOptForBlob
- Type
- bool
- Default
- 1
- Range
- 0|1
Defines whether a poll query optimization is used for blobs (default = yes).
[mod] requestDelay
- Type
- uint
- Default
- 0
- Range
- >= 0
Time in milliseconds, which must be between two requests. The value should not be set to
high, because it reduces data throughput. This entry is only relevant if gateways are
involved.
[mod] simUnicosEvents
- Type
- unsigned
- Default
- 24
- Range
- 1..24
The parameter specifies the number of items for a simulated Event Report.
[mod] simUnicosPlc
- Type
- bool
- Default
- 0
- Range
- 0|1
Determines if the master should send UNICOS frames for specific, normally unused function
codes. If you specify the function code 120 in to a peripheral address, a data status frame
containing arbitrary data is generated. If you specify the function code 121, an Event
Report frame containing arbitrary data is generated.
Used only for TEST PURPOSES.
The function code is used to inform the driver to generate a UNICOS frame. The code is not
sent outside.
[mod] statCheckInterval
- Type
- uint
- Default
- 20 [s]
- Range
- 5-100
Time interval where request statistic datapoint elements are written by the driver.
[mod] suspendTimeFactor
- Type
- int
- Default
- 10
- Range
- 1-100
If there are several RTU slaves behind a gateway and one or more of this slaves does not
reply, the communication to the failing slaves is suspended for an interval of
suspendTimeFactor*transactionTimeout to avoid big performance degradation of the
communication to the remaining available slaves.
[mod] tcpConnectTimeout
- Type
- unsigned
- Default
- 2000 [ms]
- Range
- >=1000
Connection timeout. When the connection is established, the driver waits until the
connection is initialized and until an acknowledgement is received from the PLC. If the
driver does not receive the acknowledgement within a timeout, the driver re-establishes the
connection. The timeout is specified using the config entry tcpConnectTimeout in the Modbus
section.
[mod] tcpReceiveBufferSize
- Type
- unsigned
- Default
- 0
- Range
- >=300
With this entry the TCP receive buffer size can be adjusted. This is only needed in
exceptional cases if an old Modbus device can not handle modern operating system TCP windows
size setting. The default setting 0 means that operating system default for receive buffer
is used. If a connection to an old device cannot be established, it might be that a low
value of e.g. 512 makes a connection possible.
[mod] tcpServerPort
- Type
- unsigned
- Default
- 0
- Range
- 0..65535
The port number of the TCP server. The driver opens a server socket for Modbus clients.
If the port is 0 the driver does not open a server socket and it is operating in client mode
only.
[mod] unicosMarker
- Type
- int
- Default
- 65535(0xFFFF)
- Range
- -1..65535
The driver decides with this reference number whether a Modbus or a UNICOS frame should
be used. The entry is deactivated with -1. In order to deactivate UNICOS completely, set the
entry to -1 (nothing may be set for addUnicosMarker!).