WCCILdata - PARAM/FATAL - Data manager does not run on primary or secondary data host

The following log message can be displayed during the runtime of the project. The log message is written to the PVSS_II.log-file.

WCCILdata (0), 2011.10.04 21:23:01.015,
PARAM,FATAL, 54, Unexpected state, main, Data manager does not run on primary or secondary data host 

The log message with symbolic names:

WCCILdata (0), <TIMESTAMP>, PARAM,FATAL, 54,
Unexpected state, main, Data manager does not run on primary or secondary data host
This log message describes that entries for the redundant system are not correct. The local hostname does not match one of the entries in the config-entry data = “<hostname1>$<hostname2> .
  • Correct the entries and specify the correct hostnames to enable the startup of the project. If no redundant system is used, the entries can be deleted from the config file.