PVSS00event - PARAM/WARNING - insertOneFwdDp, duplicate element ignored

Enclosed you'll find the explanation for a log-message which can occur during startup of the event-manager. The log-message is written to the PVSS_II.log-file.

PVSS00event (0), 2012.10.10 08:31:54.259, PARAM,WARNING, 54, Unexpected state, EvManager, insertOneFwdDp, duplicate element ignored: _Dnp3Station.Configuration


Log-message with symbolic names:

PVSS00event (0), <TIMESTAMP>, PARAM,WARNING, 54, Unexpected state, EvManager, insertOneFwdDp, duplicate element ignored: <DP-element>


At <DP-element> a DP-element or a DP-type + element is given.
This log-message describes that the config-entry fwdDp for the given DP-element or fwdDpType for the given DP-type + element is defined more than once in the config, config.level or config.redu-file in your project or any of the sub-projects including the config.level and config.redu file for the installed version.

It has no negative effect to the project. Nevertheless you should check and correct the config-files to avoid this error.

Most of the time this error occurs because of copying the config.redu-file from the installed version into the project directory. The standard settings are already made at the config.redu-file and there is no need to define them again at the config.redu-file in your project.

Date added:
Last revised:
Hits:
5.809
Rating:
Rating: 3.0. 51 vote(s).
51 anonymous votes
No rating done at all.
Your vote was '' (0 of 5) You are an anonymous user.
You may log on to do personalized votings
Click the rating bar to rate this item Please log on to do ratings
  • Notification

    FE user cannot be identified! (1403201096)