PVSS00event - PARAM/INFO - EvDpManager::dpFuncInit - config inactive

Enclosed you'll find the explanation for a log-message which can occur during startup of the project. The log-message is written to the PVSS_II.log-file.


PVSS00event (0), 2012.05.29 11:23:31.512, PARAM,INFO, 0, , DP: System1:Pump1.info.value:_dp_fct, MAN: (SYS: 1 Event -num 0 CONN: 1), EvDpManager::dpFuncInit - config inactive


Log-message with symbolic names:

PVSS00event (0), <TIMESTAMP>, PARAM,INFO, 0, , DP: <DPE-name>:_dp_fct, MAN: (SYS: 1 Event -num 0 CONN: 1), EvDpManager::dpFuncInit - config inactive


This log-message describes that the datapoint-function at the given dp-element <DPE-name> is “inactive” and no calculation will be made during runtime.
This error can occur if a _dp_fct-config was added without additional configuration (input-parameters, function).
To get rid of this error please check the configuration of the datapoint function. If the datapoint-function is not needed at this dp-element please remove the config.

Date added:
Last revised:
Hits:
8.945
Rating:
Rating: 3.2. 114 vote(s).
114 anonymous votes
No rating done at all.
Your vote was '' (0 of 5) You are an anonymous user.
You may log on to do personalized votings
Click the rating bar to rate this item Please log on to do ratings
  • Notification

    FE user cannot be identified! (1403201096)