WCCOAtoolCMactivation - Restore

Note:
Create a new container before restoring a license.

Windows:

cmu32 -i -f c:\Siemens\Automation\WinCC_OA\<version>\data\license\ETM_pc_-_A_Siemens_Company.WibuCmLif

Linux:

cmu -i -f /opt/WinCC_OA/<version>/data/license/ETM_pc_-_A_Siemens_Company.WibuCmLif
  • Restore without "Accept":

    Windows/Linux:

    WCCOAtoolCMactivation -interactive yes -restore 211648,211668 -serial 130-111222333 https://license-portal.example.com/12345/gateways XXXXX-XXXXX-XXXXX-XXXXX-XXXXX
    Error code: 31

    Error text: operation "restore" requires acceptance of the rules and regulations by using the additional option "-accept"

  • Restore with "Accept":

    Windows/Linux:

    WCCOAtoolCMactivation -accept -interactive yes -restore 211648,211668 -serial 130-111222333 https://license-portal.example.com/12345-dev/gateways XXXXX-XXXXX-XXXXX-XXXXX-XXXXX
  • Restore attempt with already used licence (restore is only possible once):

    Windows/Linux:

    WCCOAtoolCMactivation -accept -interactive yes -restore 211648,211668 -serial 130-444555666 https://license-portal.example.com/12345-dev/gateways XXXXX-XXXXX-XXXXX-XXXXX-XXXXX
    Error code: 12

    Error text: at least one of the licenses "211648,211668" does not belong to the given container or is not restorable or is currently activated to the given cmcontainer