What is the correct S7 driver slot configuration when working with an additional communication processor ?
The slot configured in the WinCC OA device panel must always be the slot where the CPU is placed. This is 2 for 315 series and 3 for 400 series. The number of the slot an external CP is placed in, is irrelevant for the configuration. This is also valid for a TSPP-Communication.