PVSS00event - PARAM/WARNING - SumAlert config does not have an id list nor an id pattern to select DP elements

Enclosed you will find the explanation for a log-massage during system start concerning duplicate elements. The log-message is written to the PVSS_II.log-file.

PVSS00event (0), 2011.01.17 08:41:28.186, PARAM,WARNING, 22, Internal consistency check for config failed, DP: dist_4:MOT_MOT_-_TERMINAL_INTERFACE_FACILITY_PIG_RECEIVER_RP-1301_1_1.Warning:_alert_hdl, MAN: (SYS: 4 Event -num 0 CONN: 1), SumAlert config does not have an id list nor an id pattern to select DP elements


Log-message with symbolic names:

PVSS00event (0), 2011.01.17 08:41:28.186, PARAM,WARNING, 22, Internal consistency check for config failed, <DP-name>, MAN: (SYS: <system number> Event -num 0 CONN: 1), SumAlert config does not have an id list nor an id pattern to select DP elements

 

The configuration of the alert_hdl-config of the appropriate datapoint is not correct. There is no DP-list or DP-pattern assigned to a sumalert. This sumalert will be ignored internally.
 

Date added:
Last revised:
Hits:
10.536
Rating:
Rating: 3.1. 65 vote(s).
65 anonymous votes
No rating done at all.
Your vote was '' (0 of 5) You are an anonymous user.
You may log on to do personalized votings
Click the rating bar to rate this item Please log on to do ratings
  • Notification

    FE user cannot be identified! (1403201096)