connection to plc "S7 1500" cannot be established or lasts too long by S7 driver

Right now it is a known behaviour when S7 driver tries to establish a connection to the plc S7-1500.

It can last some time (sometimes up to several minutes).

In this case set the config entry [s7] UseConnections = 1 and start the driver once again.

Using this config entry the time to establish a connection to the plc can be decreased.

 