[s7]
Settings for the S7 driver
[s7] AliveInterval
- Type
- unsigned
- Default
- 30
- Range
- 0..65535
[s7] AutoGQ
- Type
- string
- Default
- Y
- Range
- Y/N
[s7] AutoTimeSyncFactor
- Type
- unsigned
- Default
- 0
- Range
- 0..x
[s7] CheckPollReqPending
- Type
- bool
- Default
- 1
- Range
- 0|1
[s7] diagnosticsRefreshTime
- Type
- unsigned
- Default
- 60 [sec]
[s7] HighPrioBlock
- Type
- int
- Default
- -1
- Range
- >-1
[s7] LimitedTSPPAliveCheck
- Type
- string
- Default
- N
- Range
- Y|N
[s7] MaxAGLinkQueueSize
- Type
- int
- Default
- 1
- Range
- 1..32
[s7] MaxGap
- Type
- unsigned
- Default
- 10
- Range
- 1..50
[s7] maxPollBlockSize
- Type
- uint
- Default
- 65535
- Range
- 32..65535
[s7] MaxReadRequestSize
- Type
- int
- Default
- 0
- Range
- 0,1, >50
[s7] MaxRequestQueueSize
- Type
- int
- Default
- 200
- Range
- 0..1000
Note:
The new values are written to DPE in the interval defined by "StatCheckInterval" config
entry. [s7] MaxTsppAnswerListSize
- Type
- int
- Default
- 200
[s7] MaxTsppRequestQueue
- Type
- unsigned
- Default
- 4
- Range
- 1..64
[s7] MaxTsppVcPerLoop
- Type
- int
- Default
- 1000
[s7] MaxWriteBlockLen
- Type
- int
- Default
- 0
- Range
- 0..240
DB10.DBW0
DB10.DBB3
DB10.DBX4.0
DB10.DBX4.1
DB10.DBX4.2
DB10.DBX4.3
DB10.DBX4.4
DB10.DBX4.5
DB10.DBX4.6
DB10.DBX4.7
are sent as a block, because the addresses are in consecutive order (there is no hole). If
e.g. the last bit is missing only the first 2 addresses are sent as block and the bits are
sent individually, because the last byte is not full. The maximumWriteBlockLen depends on
the used PLC type. If the value is below 240 bytes, you can be sure that the generated
request is not split by the used S7 communication library. [s7] MaxWriteGroupSize
- Type
- int
- Default
- 16
- Range
- 1..64
[s7] onlyActivePolls
- Type
- string
- Default
- N
- Range
- Y/N
[s7] plcCodePage
- Type
- string
- Default
- <langgt;.iso88591
If strings in the PLC are encoded with a specific language encoding, this config entry can be used to define the base encoding for the conversion to UTF-8.
All valid encoding values for this config entry can be found in the file <Install Directory>/nls/lang.dir.
Example
[s7]
plcCodePage = "el_GR.iso88597"
[s7] ReadOpState
- Type
- uint
- Default
- 15
- Range
- >=0
The different states are:
- 0 STOP
- 1 START-UP
- 2 RUN
- 3 UNDEFINED
- 8 RUN SOLO (one PLC is running)
- 9 RUN REDU (both PLCs are running)
- 10 HALT
- 11 CONNECTING
- 12 UPDATING
[s7] ReadPLCTime
- Type
- string
- Default
- N
- Range
- Y/N
[s7] reduModeTSPP
- Type
- bool
- Default
- 0
- Range
- 0|1
[s7] refreshPollBlocksOnUse
- Type
- string
- Default
- N
- Range
- Y|N
[s7] setInvalidForConnLoss
- Type
- uint
- Default
- 1
- Range
- 0 - 2
[s7] StatCheckInterval
- Type
- unsigned
- Default
- 20 [sec]
- Range
- 5..100
[s7] TimeSyncUTC
- Type
- string
- Default
- N
- Range
- Y/N
[s7] UseConnections
- Type
- int
- Default
- 2
- Range
- 1,2,3
[s7] useStringLengthInfo
- Type
- string
- Range
- Y|N