PVSS00event - PARAM/WARNING - Datapoint type does not exist, EvManager, appendCopyList

Enclosed you'll find the explanation for a log-message which can occur during startup of the event-manager. The log-message is written to the PVSS_II.log-file.

PVSS00event (0), 2012.11.15 11:12:52.255, PARAM,WARNING, 57, Datapoint type does not exist, EvManager, appendCopyList, _Engine


Log-message with symbolic names:

PVSS00event (0), <TIMESTAMP>, PARAM,WARNING, 57, Datapoint type does not exist, EvManager, appendCopyList, <DP-type>


This log-message describes that a non-existing DP-type was defined at a copyDpType entry in the config, config.level or config.redu-file in your project or any of the sub-projects including the config.level and config.redu file for the installed version.

Please check the settings for your project and remove the entry if it is not needed or create the necessary datapoint-type to get rid of this error.